1400FS FUEL STATION

1400FS FUEL STATION
Self-contained ? diesel fuel depot with integrated bunding. Complete fuel management for farms, construction sites and commercial fleets.
Estimate delivery costs
Your Eircode lets us show an accurate delivery cost before checkout.
Harlequin Manufacturing Ltd (Euro)
What makes this STATION the right choice?
1400FS FUEL STATION
Fuel Stations provide forecourt style refuelling convenience and come complete with a range of added value technologies as standard. Ideal for the bunded storage & dispensing of Diesel Fuel and B5 Bio-Diesel.
Designed specifically to satisfy the fuel storage requirements of agricultural, commercial and industrial diesel users.
The 1400FS model consists of a Bunded Plastic Diesel Storage and Dispensing Tank, moulded from Medium Density Polyethylene and supplied complete with:
- 2" BSP Lockable Fill Point with Screw Cap and Chain
- 4" Lockable Inspection Point with Screw Cap
- Choice of 12v (56lpm), 24v (56lpm), 110v (56lpm), 240v (56lpm) or 240v (72lpm) Electric Pump
- 10 micron Integrated Particulate and Water Filter
- Mechanical Flow Meter with Resettable Batch Totaliser
- Weatherproof Fuel Tank Vent
- Oil Tank Contents Dipstick
- Electronic Oil Tank Contents Gauge
- LRC Failsafe Oil Tank Overfill Prevention Device
- Lockable Access
- 4 metre Fuel Delivery Hose with Three Stage Automatic Shut Off Nozzle
- Bulkhead Light - 240v Models only
- Factory Fitted Electrical Connection Point - 240v and 110v Models only
- Battery Fly Leads - 12v and 24v Models only
*DELIVERY TERMS:
Tail-lift deliveries are available for most tanks up to 2,500 Litre capacities for kerbside delivery subject to availability.
It is the responsibility of the customer to inform us, if off-loading equipment is required.
Technical data
Full specifications
| Physical | |
| Capacity | 1423 L |
| L × W × H | 161 × 157 × 188 cm |
| L × W × H (mm) | 1610 × 1570 × 1880 |
| Empty weight | 150 kg |
| Construction | |
| Material | MDPE |
| Reference | |
| SKU | 1400FS |
| EDEL code | EDELP00002251 |
Irish regulations
Installation & requirements
OFTEC regulation
All domestic oil tank installations in Ireland must be carried out by an OFTEC-registered technician. The tank must conform to IS:293 and be sited in accordance with IS:820.
Site requirements
The tank must stand on a level, load-bearing concrete base minimum 100 mm thick, extending 300 mm beyond the tank footprint on all sides. Ground must be clear of vegetation.
Bunding requirements
Bunded tanks are required within 10 m of a watercourse or drain. Secondary containment must hold 110% of the inner tank capacity. Check local planning conditions before installation.